Slide 1 of 5
NEW
MIC-RS3
Index: WMGBMICRS3
Insulation resistance meter
    Description
    Technical specification
    Standard accessories
    Files
    • Description

      Designed for the industry

      The instrument is dedicated for companies and sites, in which continuous or random assessment of the insulation resistance is required as part of production. It is also perfect for automated production systems.

      The meter can be installed in the distribution board, at the operator’s station (assembly or quality control bench), in the control cabinet or even in the rack enclosure. It can be controlled by switchgear management devices, such as Siemens S7 Simatic controllers. The measurement is performed by means of clamps, used to connect the test leads of the system, in which the instrument is installed.

      It is possible to prepare a version of the meter with the interface and communication protocol requested by the customer.

      Features

      • Measurement voltage selected within the range of 50…5000 V
      • Automatic discharge of the measured object’s capacitance upon completion of insulation resistance measurement
      • Measurement current 1.4 mA
      • Protection against measurement of live objects

      Additional features

      • Capacitance measurement after measurement of RISO
      • RS-485 interface
      • Data transmission to a controlling device through the MIC-RSx-SCP or Modbus communication protocol
      • External power supply
      • The instrument meets the requirements laid down by standard EN IEC 61557

      Features

      The meter is designed for building in/permanent installation. It plays a Secondary/Slave role, meaning that it executes the commands issued by the Main/Master control device and it does not initialise the transmission on its own. It enables measuring the insulation resistance with the test voltage of up to 5000 V.

      There are two measurement modes available: automatic (continuous) and manual (one-time). Under automated testing, the meter can be programmed to measure the capacity or not.

      Response and communication

      The meter is operated from the Main/Master control device by means of the MIC-RSx-SCP serial communication protocol or Modbus protocol. It enables, for example, starting and stopping the measurement of resistance, reading the measurement result or changing the configuration of the instrument.

    • Technical specification

      Insulation resistance measurement


      Measurement range acc. to IEC 61557-2

      for RISOmin = (UISOnom / IISOnom)…5000 GΩ (IISOnom=1.4 mA)

      Range Resolution Accuracy
      0.0…999.9 kΩ 0.1 kΩ ±(3% m.v. + 20 digits)
      1.000…9.999 MΩ 0.001 MΩ ±(3% m.v. + 20 digits)
      10.00…99.99 MΩ 0.01 MΩ ±(3% m.v. + 20 digits)
      100.0…999.9 MΩ 0.1 MΩ ±(3% m.v. + 20 digits)
      1.000…9.999 GΩ 0.001 GΩ ±(3% m.v. + 20 digits)
      10.00…99.99 GΩ 0.01 GΩ ±(3% m.v. + 20 digits)
      100.0…999.9 GΩ 0.1 GΩ ±(3% m.v. + 20 digits)
      1.000…5.000 TΩ 1 GΩ ±(4% m.v. + 50 digits)

      “m.v.” - measured value

      Values of measured resistance depending on measurement voltage


      Voltage UISO Measurement range
      0…100 V 50 GΩ
      200 V…400 V 100 GΩ
      500 V…900 V 250 GΩ
      1000 V…2400 V 500 GΩ
      5000 V 5000 GΩ
    • Standard accessories
    • Files