S-110 DC
Index: WMGBS110DC
High Voltage Insulation Tester
    Description
    Technical Specification
    Optional accessories
    Files
    • Description

      MV and HV insulation under full control

      The S-110DC device is a universal high voltage tester. It is extremely durable, but also lightweight, compact and easy to carry due to its transport case on wheels.

      Capacitive objects, such as shielded power cables, will be correctly and automatically discharged by the integrated discharge module if an error occurs or the test time expires. A key switch, a switch-on lock and a protective earthing circuit ensure maximum safety.

      Sonel offers online training course on the use of this product (instructional video and consultation with a specialist).

      Features

      • Easy operation
      • Robust construction, low weight
      • Integrated timer:
        • max. 60 min 
      • •Discharge device:
        • external ground-discharge rod 
      • Voltage measurement direct at HV output
      • Short-circuit-proof output:
        • protection by overcurrent tripping
      • Protective ground connection

      Fields of application

      • Testing at recommissioning of cable systems after maintenance and repair
      • Testing of newly installed cables an cable joints before commissioning
      • Regular preventive cable testing 
      • Testing of electrical equipment
    • Technical Specification

      Technical specification


      S-25 DC S-50 DC S-80 DC S-110 DC S-120 DC
      Power supply • internal rechargeable battery • mains, switchable 115 / 230 V, 50-60 Hz • external DC voltage source mains 230 V / 50 Hz (optional: 115 V / 60 Hz mains 230 V / 50 Hz (optional: 115 V / 60 Hz mains 230 V / 50 Hz (optional: 115 V / 60 Hz mains 230 V / 50 Hz (optional: 115 V / 60 Hz
      Power consumption max. 120 VA max. 900 VA max. 900 VA max. 900 VA max. 900 VA
      Output voltage • 0…25 kV DC • infinitely adjustable • negative polarity • ripple < 0,25% • 0…50 kV DC • infinitely adjustable • negative polarity • 0…80 kV DC • infinitely adjustable • negative polarity • 0…110 kV DC • infinitely adjustable • negative polarity • 0…120 kV DC • infinitely adjustable • negative polarity
      Rated output current at max. output voltage 1.5 mA electronically limited 6 mA 5 mA 4 mA 3,5 mA
      Battery operation at full load 45 min - - - -
      Discharge - integrated automatic discharge device 3000 J 9.6 µF at 25 kV 7500 J 6 µF at 50 kV 12 250 J 4 µF at 75 kV 3.5 µF at 80 kV 15 000 J 3 µF at 100 kV 2.5 µF at 110 kV 18 750 J 2.4 µF at 125 kV 2.6 µF at 120 kV
      Voltage measuring range 0…30 kV 0…50 kV 0…80 kV 0…110 kV 0…130 kV
      Current measuring ranges 0…200 µA / 0…2 mA manual or automatic switching between ranges 0…100 μA / 1 mA / 10 mA manual switching between ranges 0…100 μA / 1 mA / 10 mA manual switching between ranges 0…100 μA / 1 mA / 10 mA manual switching between ranges 0…100 μA / 1 mA / 10 mA manual switching between ranges
      Operating temperature -25…+55°C
      -13…+131°F
      -25…+55°C
      -13…+131°F
      -25…+55°C
      -13…+131°F
      -25…+55°C
      -13…+131°F
      -25…+55°C
      -13…+131°F
      Storage temperature -40…+70°C
      -40…+158°F
      -40…+70°C
      -40…+158°F
      -40…+70°C
      -40…+158°F
      -40…+70°C
      -40…+158°F
      -40…+70°C
      -40…+158°F
    • Optional accessories
    • Files